OVERVIEW |
UPC Code |
037332224125 |
UPS Type |
On-Line |
INPUT |
Rated input current (Maximum Load) |
61A |
Nominal Input Voltage(s) Supported |
220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye |
Nominal Input Voltage Description |
3-Phase Wye, 4 wire plus ground (L1, L2, L3, N, G) |
UPS Input Connection Type |
Hardwire |
Input Circuit Breakers |
80A (3 pole) |
Input Phase |
3-Phase |
Power Factor (Input) |
.99PF (100% load) |
THDi |
<3% (100% load) |
OUTPUT |
Output Volt Amp Capacity (VA) |
40000 |
Output kVA Capacity (kVA) |
40.00 |
Output Watt Capacity (Watts) |
36000 |
Output kW Capacity (kW) |
36.00 |
Output Capacity Details |
Supports up to 100% load continuously in double conversion mode; Supports 100-110% load for 10 minutes, 110 to 130% load for 1 minute and greater than 130% for 1 second before switching to bypass mode; Inverter mode is automatically restored as load levels are reduced to less than 70%; Configuration options support up to 3 S3M40KX-NIB systems wired in parallel for increased capacity or fault-tolerant, redundant operation |
Power Factor |
0,9 |
Crest Factor |
3:1 |
Frequency Compatibility |
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
Frequency Compatibility Details |
Automatic frequency selection |
Output Voltage Regulation (Line Mode) |
+/- 1% |
Output Voltage Regulation (Economy Line Mode) |
+/-11V of nominal |
Output Voltage Regulation (Battery Mode) |
+/- 1% |
Output AC Waveform (AC Mode) |
Pure Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
Nominal Output Voltage(s) Supported |
220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye |
Output Receptacles |
Hardwire |
Individually Controllable Load Banks |
No |
BATTERY |
Expandable Battery Runtime |
Supports extended runtime with optional external battery packs |
Expandable Runtime |
Yes |
External Battery Pack Compatibility |
BP480V09 ; BP480V10 ; BP480V10 -NIB; BP480V100 ; BP480V100 -NIB; BP480V40 ; BP480V40 -NIB; BP480V65 ; BP480V65 -NIB |
DC System Voltage (VDC) |
+/- 240 |
Battery Recharge Rate (Included Batteries) |
9 hours to 90% (Internal batteries) |
VOLTAGE REGULATION |
Voltage Regulation Description |
Online, double-conversion power conditioning maintains output within 1% of the selected nominal voltage in online mode |
USER INTERFACE, ALERTS & CONTROLS |
Front Panel LCD Display |
LCD DISPLAY: offers a variety of graphical, text and numeric information to indicate a wide range of UPS operation and fault / warning conditions, including current operating mode, alarm status, load level, battery charge, input / output voltage & frequency, estimated runtime and more (see user manual for a detailed listing) |
Switches |
ON / ENTER BUTTON: turns the UPS on and confirms a selection from the settings menu; OFF / ESC BUTTON: turns off the UPS and returns to the previous item in the settings menu; TEST / UP BUTTON: initiates UPS self-test operation and advances to the next item in the settings menu; MUTE / DOWN BUTTON: silences the audible alarm and advances to the previous item in the settings menu; Press TEST/UP & MUTE/DOWN buttons simultaneously for 1 second to enter or exit the settings menu (See user manual for detailed information) |
Audible Alarm |
Alarms warn users of a variety of operational conditions: BYPASS MODE (beeps every 2 seconds), BATTERY MODE (beeps every 4 seconds), FAULT MODE (beeps continuously), OVERLOAD (beeps twice per second), OTHER WARNINGS (beeps once per second), FAULT (beeps continuously); All alarms can be silenced, except OVERLOAD & OTHER WARNINGS conditions |
LED Indicators |
4 LEDs report BYPASS / LINE / BATTERY / FAULT modes |
PHYSICAL |
Cooling Method |
Fans |
Installation Form Factors Supported with Included Accessories |
Tower |
Primary Form Factor |
Tower |
Primary UPS Depth (mm) |
815 |
Primary UPS Height (mm) |
1,000 |
Primary UPS Width (mm) |
300 |
Shipping Dimensions (hwd / in.) |
47.44 x 16.90 x 36.22 |
Shipping Weight (lbs.) |
222.50 |
UPS Housing Material |
Steel |
UPS Power Module Dimensions (Height x Width x Depth, mm) |
1000 x 300 x 815 |
UPS Power Module Dimensions (hwd, in.) |
39.37 x 11.81 x 32.08 |
UPS Power Module Weight (kg) |
80.29 |
UPS Power Module Weight (lbs.) |
177.0 |
ENVIRONMENTAL |
Operating Temperature Range |
0 to +40C (32-104F) |
Storage Temperature Range |
0 to +35C (32 to 95F) with battery; -15 to 60C (5 to +140F) without battery |
Relative Humidity |
5 to 95%, non-condensing |
Operating Elevation (ft.) |
< 3280ft (Capacity de-rates by 1% for every 328ft over 3280ft ) |
Audible Noise |
<60dBA at 1meter |
Operating Elevation (m) |
< 1000m (Capacity de-rates by 1% for every 100m over 1000m) |
COMMUNICATIONS |
Network Management Cards |
WEBCARDLX ; MODBUSCARDSV ; RELAYCARDSV |
Network Monitoring Port Description |
Card accessory slot supports network management interface or programmable I/O relay card options |
Communications Cable |
DB9/RS-232 cable included |
Communications Interface |
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
LINE / BATTERY TRANSFER |
Transfer Time |
Zero transfer time Online to Battery, Inverter to Bypass 0ms (Synchronous), and Inverter to ECO mode < 10ms. |
Low Voltage Transfer to Battery Power (Setpoint) |
120V (Ph-N), 208V (Ph-Ph) @50% load / 176V (Ph-N), 305V (Ph-Ph) @100% load |
High Voltage Transfer to Battery Power (Setpoint) |
276V (Ph-N), 478V (Ph-Ph) @ 50% or 100% load. |
SPECIAL FEATURES |
Grounding Lug |
Yes |
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Automatic inverter bypass; Manual bypass switch; Auto Probe Monitoring (requires WEBCARDLX); Zero transfer time; On-Line/Double-Conversion |
Green Energy-Saving Features |
High efficiency economy mode operation |
STANDARDS & COMPLIANCE |
UPS Certifications |
CE |
Certification Details |
IEC/EN 62040-1:2008+A1 (Safety); IEC/EN 62040-2:2006 (Category C3) |
WARRANTY |
Product Warranty Period (U.S. & Canada) |
1-year limited warranty |
3-Phase Warranty Statement |
Tripp Lite 3-Phase UPS Factory Warranty |